Classes, sub-items, Modbus loopback and OPC UA loopback pass on R1.05. New examples/CI-Eng-Sample/shared/: snapshot, reduced load/remove, test and DSS temp-file cleanup scripts for shared servers. Before/after snapshot identical; ISS-091 (dss_*.tmp left in tls\lst); ISS-080 note. Certificate files of the test await deletion by the user. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
39 KiB
Progress
Status of each manual and each practiced task. Update this file as work proceeds.
Manual status: not started · summarized · in practice · done Task status: not practiced · practiced, awaiting confirmation · passed · not completed (see notes) Sample column: whether the task has been re-tested on CI-Eng-Sample: n/a (needs no project data) · pending (tested on AID only) · added (sample content built) · passed
A task is done only when Status is passed and Sample is passed or n/a. Then AID is no longer needed to repeat it.
Test system
Practice notes refer to the repo author's development test system, not to anything shipped with this repo:
- R1.03 work (phases 0–13): CI Server R1.03.00, unlicensed, on the development machine.
- R1.05 work (from 2026-10-08): CI Server R1.05.00, licensed, on a remote test server reached
by ssh. The server is shared with other projects: checks there are read-only unless the
user approves a change; no CI Server restarts; never touch other projects' records or live
plant values; check
query userand recent audit-trail writes before a test that changes anything; remove scratch files afterwards. LoadingCI-Eng-Samplethere needs the user's approval first. - AID (e.g.
AID.WRPS.SIM.INFLOW) is the author's own test project on that machine. It is not in this repo and other systems will not have it. Item names here are evidence of what was tested, not names to use elsewhere. - Communication stations seen there (
WRPS_PLC,MODSIM_STATION,STN_MQTT) belong to AID.
Tasks may be practiced first on AID, but everything they need is then added to the sample
project CI-Eng-Sample (examples/CI-Eng-Sample/) and re-tested there, so that in the end
AID is not needed.
R1.05 re-check
main moved to R1.05 on 2026-10-08; the R1.03 state is frozen on branch r1.03 (tag
r1.03-final). All the status below was reached on R1.03. Each skill is re-checked on
R1.05 in the order of version-differences.md §3. Then its front matter gets version: R1.05
and its row here is updated.
R1.05 status: not started · manual diff read · re-checked (read-only) · re-tested · done
Two labels for checks Claude cannot do (details and steps in
r105-verification.md): not tested = the function is not
available on the R1.05 test server (reason given); awaiting user verification = Claude
prepared the step and the user runs it on the server or in the GUI and sends the output or a
screenshot.
| Skill / area | Manual changes after R1.03 | R1.05 status | Notes |
|---|---|---|---|
system-check |
— | re-checked (read-only) | Version, paths, service, node, time on the R1.05 test server 2026-10-08. Start/stop not repeated (shared server). |
installation-security |
C10, C30 (large: IT security 3.0, LAPS, upgrade merge jupgutl, PRM) |
re-checked (read-only) | 2026-10-08: skill, summaries and tools/setup_check.ps1 updated to R1.05. Setup check run by hand on the R1.05 test server. Script run there too (12 OK, 5 CHECK, 20 DIFF; firewall check fixed). Not tested: IT security 2.0/3.0, LAPS, Vnet/IP, upgrade merge, PRM (not available there). ISS-086–090. |
data-access |
L45, E20 (large: REST API, OPC UA methods, information model mapper, certificate expiry, extended functions off by default), L50 dataset rename | re-checked (read-only) | 2026-10-08: skill and summaries updated, L45 section numbers remapped. Setup files, datasets, ports and certificates checked; Sample qli files unchanged. New form fields confirmed in the installed form definitions (V3); OPC UA loopback re-tested on R1.05 with the reduced sample load (V4, 2026-10-08), certificate exchange done by the user. Not tested: OPC A&E direct alarms, PubSub, imported information model. ISS-080–085. |
equipment |
L41 (IEC 61850, item status, App. 1); IEC 104/61850 drivers moved to eqt/eta |
re-checked (read-only) | 2026-10-08: Modbus datasets, setup files and tools identical to R1.03; EQT family, IEC 61850 report control blocks and upgrade steps added. Sample qli files unchanged. eqpdbg main info run on R1.05 (V1); Modbus loopback re-tested on R1.05 with the reduced sample load (V4, 2026-10-08). Not tested: IEC 104 / IEC 61850 and the EQT tools (no device). ISS-076–079. |
| pyTOOLS (new) | P40 new | not started | No skill yet. |
graphics |
C50, C60, R30 (small) | manual diff read | |
history-management |
C40 §4.2 (REST API, pyTOOLS) | manual diff read | The REST API itself is described in skill data-access (L45 ch. 4); link to it from here. |
portal-setup |
R10 §3.3 | manual diff read | |
system-management |
J10 §2.9.1, L50 | manual diff read | |
item-engineering |
C10 §2.2 | manual diff read | |
alarm-management |
none | not started | |
audit-trail |
none | not started | |
authorization |
none (new dss_ath_grp_u0104 loader) |
not started | |
class-object-engineering |
none | not started | Sample classes CIENG_INCR, CIENG_TANK (traditional) and CIENG_JFLOW (Java) loaded and ran correctly on R1.05 (V4, 2026-10-08). |
high-availability |
none | not started | |
reporting |
none | not started | |
examples/CI-Eng-Sample |
— | re-tested | Reduced load (no history group, user or layouts) loaded, tested and removed on the shared R1.05 server 2026-10-08 (V4); scripts in shared\. Full load not tested on R1.05. |
Manuals, in working order
| Phase | Manual | Title | Status |
|---|---|---|---|
| 0 | IM 36K01A50 | Release Information | summarized (notes) |
| 1 | IM 36K10J10 | System Design/Management | done except migration (not practiced; needs a second system) and debugging tools; skill system-management (notes) |
| 2 | IM 36K01C10 | CI Server Setup | summarized (notes); skill installation-security |
| 2 | IM 36K01C30 | Security Guide | summarized (notes); skill installation-security |
| 3 | IM 36K10G10 | Tutorial | summarized (notes); command-line equivalents practiced on CI-Eng-Sample |
| 4 | IM 36K10R10 | CI Portal Setup | done except separate CI Portal node (needs a second node); skill portal-setup (notes) |
| 4 | IM 36K10R20 | Setup File Editor | done; Templates tab and Undo Field not explored (notes, ISS-016) |
| 5 | IM 36K10C10 | Engineering Module - I/O Processes | summarized (notes); default datasets checked read-only |
| 5 | IM 36K10L40 | EQUIPMENT Service - Utilities | summarized (notes); eqpdbg main info run read-only |
| 5 | IM 36K10L41 | EQUIPMENT Service - Configuration | summarized (notes); general + Modbus in detail, other drivers as a table |
| 5 | IM 36K10L35 | ITEM Service - ITH | summarized (notes); installed processes and setup files checked |
| 5 | IM 36K10L36 | ITEM Service - ITM | summarized (notes); itmdbg statistics run; itmval -f crashes (ISS-022) |
| 6 | IM 36K10L10 | Class/Object Engineering | done; opc.sup read-only, opcdbg read-only actions and Reset class practiced (notes); skill class-object-engineering |
| 6 | IM 36K10P10 | Class Description Language - Traditional | done for prompts, signals, created items, transitional operators, PRINT/ERROR; timers, alarms, containment, STEP, DSS routines, AGA from docs (notes) |
| 6 | IM 36K10P11 | Class Description Language - Java | done for a basic class (attach/create items, signal trigger, systemMessage); timers, containment, inheritance from docs (notes) |
| 7 | IM 36K10L55 | Exchange Tool Engineering | summarized, from docs only (needs CENTUM VP / RGS or Prodigy) (notes) |
| 7 | IM 36K10L30 | BUS Service | done for single-node checks; MDUR, encryption, logical addresses, printer devices from docs (notes); task system-management/bus-utilities.md |
| 7 | IM 36K10L45 | Data Access Engineering | done for OPC UA client/server (loopback); OPC DA/A&E from docs (DA loopback not allowed); ODBC not running (ISS-008) (notes); skill data-access |
| 7 | IM 36K10E20 | OPC Interface | summarized; OPC UA point form compared with quick load by the user (notes) |
| 8 | IM 36K10L15 | Alarm Management Engineering | done for item-based alarms (ack type, AOI, ASA, events, acknowledge, delay/repeat, almdbg/alhdbg); first-out, collections, notifications, shelving, acoustic/count destinations from docs (notes); skill alarm-management |
| 8 | IM 36K10C20 | Engineering Module - Alarms | done by quick load for item alarm fields, ack types, AOI, ASA; forms, overviews, shelving, link display, notifications, external/Vnet alarms from docs (notes) |
| 8 | IM 36K10E30 | Alarm System Performance Analysis | summarized, from docs (ASPA GUI not practiced; launcher and fetch limits checked) (notes) |
| 9 | IM 36K10L20 | History Management Engineering | done for hisdbg checks, files and rollover; archive and repair utilities from docs (notes); skill history-management |
| 9 | IM 36K10C40 | Engineering Module - Historical | done by quick load for Event/Item, Scan/Time and Aggregation groups (aggregation needs a higher-priority source group, ISS-040); archive from docs (notes) |
| 10 | IM 36K10R30 | Graphic Display Setup | done for HTML display, folders and layouts (phase 10b: desktop and web); dataset forms, form language, dual screen from docs (notes); skill graphics |
| 10 | IM 36K10C50 | Edit Module | done for one display (built by the user) and jwuiutl validate/search/export; other components, symbols, actions from docs (notes) |
| 10 | IM 36K10C60 | Advanced Operating Graphics | summarized, from docs (AOG displays checked read-only) (notes) |
| 11 | IM 36K10L50 | Data Set Service Engineering | done for DSS processes, dss.sup, quick load directives (macro, include, memo from file), dssutl read; dssana.sup covered by skill authorization (notes); task system-management/dss-tools.md |
| 11 | IM 36K10P30 | Data Set Service Language | summarized; compiler used as syntax check on a copy (no dictionary change) (notes) |
| 11 | IM 36K10P20 | Report Generation Language | done for queries, layout, cursors/loops, functions, SPOOL/CSV, HTML; SEND/RECEIVE, BREAK, INCLUDE, FLAG PAGE from docs (notes); skill reporting |
| 11 | IM 36K10R40 | Report Server Setup | done for processes, set-up files, interactive generator, rptstp; extra generators, separate RPI servers, custom destinations from docs (notes) |
| 11 | IM 36K10C30 | Engineering Module - Reporting | done by quick load for report definitions (ad hoc + parameters, schedule, item trigger, HTML, logbook), generated reports and a file device/destination; Engineering Module forms, generate and view checked by the user; report component in displays and hardcopy printers from docs (notes) |
| 11 | IM 36K10E10 | Excel Add-in | summarized, from docs (Excel not installed on the test system) (notes) |
| 12 | IM 36K10L25 | Audit Trail Management | done for processes, classifiers, AUDIT_TRAIL reading/export, audit report, selection groups, ADTLOG (default and filtered); distributor, extra collectors, classifier extension in C and operator-side ITEM.* events from docs (notes); skill audit-trail |
| 13 | IM 36K10J20 | High Availability Computing | summarized from docs; installed hac.sup, scripts, executables and HMI properties checked read-only (single unlicensed server, HAC not licensed) (notes); skill high-availability |
| 13 | IM 36K10J40 | Active Directory Integration | summarized from docs; installed dssana.sup AD/SSO/login settings, USER_DF fields and auth\WEB-INF templates checked read-only (no domain) (notes); skill authorization |
| — | IM 36K01A10 / A20 / A30 | Read Me First, License, OSS terms | skipped (no engineering content) |
Order change after reading IM 36K10J10: its migration procedure (§5.6) shows the dependency chain communication lines/stations/points → installations/units → items (template items first) → storage groups → classes → objects → reports. So acquisition and items (phase 5) now come before classes and objects (phase 6), and the other interfaces follow as phase 7.
Tasks
| Manual | Task | Status | Sample | Notes |
|---|---|---|---|---|
| J10 | System check: version, paths, running state, time sync (skill) | passed | n/a | Started CI Service elevated; live version R1.03.00; node UNLICENCED (expected). |
| J10 | Time sync check (w32tm); DURUTL configuration (durutl.sup) |
passed (check); configuration not practiced | n/a | w32tm check verified in system-check. durutl.sup has no active settings (single node, not a time master); configuring DURUTL needs a second node, so not practiced. |
| J10 | Export a dataset with dssqld (task) |
passed | n/a | Filtered export (@SELECT) passed (ISS-003, closed). |
| J10 | Import and delete dataset records with dssqld (-i, -r) (task) |
passed | passed | Built CI-Eng-Sample: 3 sections + 4 items imported, removed and re-imported with 0 errors. 2026-09-30 later: -m (update, used to set a storage group stop time) and loading/removing storage groups passed; see ISS-005. |
| J10 | Read an item with itmval -g (task) |
passed | passed | Read AID.WRPS.* items. -a 1..5 gave ITM-E-WRONG_ATT on an item without limits; works on items with limits (ISS-004, closed). |
| J10 | Write an item with itmval -p (task) |
passed | passed | Sample: TANK1.INFLOW 120.5 then 130 with -s 9, PUMP1.RUNNING 1 (status 5 BOOLEAN 1); no uoff flag. AID: AID.WRPS.SIM.INFLOW 419.76 → 400 → 419.76. After the first write the item's options gained the uoff flag (0x8a → 0x8e) = updated offline, option bit 4 (written while its station was offline). See ISS-001, closed. |
| J10 | Read the message log (tls\log\umhlog.log) |
passed | n/a | |
| J10 | Per-component version list (tls\lst\tls_versions.lst) |
passed | n/a | |
| J10 | Load history from CSV with ithloahis; read history back with dssqld (task) |
passed | passed | Sample storage group CIENG_EVENT (Event/Item). SCAN file (LEVEL 61–63, INFLOW 101–103) and EVENT file (LEVEL 47, 48) stored and read back via ITEM_HISTORY. New groups need a CI Server restart before they store; samples dated before the current storage unit were not stored (ISS-006). |
| J10 | Consistency check (dsschk, ismchk) (task) |
passed (check); repair and ismchk not practiced |
n/a | dsschk -e -v (check only) reports each of 228 datasets, no problems. Plain dsschk prints nothing on a single node. ismchk needs a database file name; not run (ISS-002, closed). |
| J10 | Monitoring processes (intmon, intcpumon, intdskmon, inttcpmon, intspawn) (task) |
passed | passed | All five worked into CI-Eng-Sample.SYSTEM.* / PUMP1.MODE, started by hand with <exe> -n <name>; setup files restored afterwards. intdskmon reports used %; intspawn command path must be short (ISS-007). |
| J10 | Backup of tls folders |
not practiced | n/a | Plan only; the actual backup tool is site-specific. |
| J10 | Migration between systems (§5.6) | not practiced | added | After phase 6 CI-Eng-Sample has every data kind in the chain up to classes/objects (items, points, storage groups, classes, objects). Export with dssqld -e works; the import into a second system is not practiced (no second system). |
| J10 | Tuning checks (read-only) (task) | passed | n/a | Read dur.sup (max processes 250), itm.sup (item pool 650,000 KB) and the automatic health snapshots tls\log\smd_*.log (common memory free, queue use per process, lock collisions). Debug launchers and interactive debuggers not practiced. |
| C10/C30 | Setup check script tools/setup_check.ps1 (task) |
passed | n/a | Read-only; 16 OK / 5 CHECK / 15 DIFF on the Win10 Pro test PC (kept as dev PC by decision). |
| C10 | Read ci_start.log and web ports (jwuiisg.sup) |
passed | n/a | All services started; SSL error ISS-008. |
| C10 | Start / stop CI Server | passed (phase 1) | n/a | Via the CI Service (elevated). Start-menu shortcuts not used. |
| C10 | New install, reinstall, upgrade, uninstall, licence | not practiced | n/a | Would reinstall or change the test system; only the installed R1.03 is available. Skipped. |
| C10 | Windows settings changes (power, virtual memory, Defender, updates, …) | not practiced | n/a | Test PC kept as a development PC (user decision 2026-09-30); not applied. |
| C10 | Vnet/IP drivers / Vnet/IP Interface Package | not practiced | n/a | No Vnet/IP card; not supported on Windows 10 Pro. |
| C30 | IT Security Tool, Domain Link Management, account utilities | not practiced | n/a | Not installed and not supported on Windows 10 Pro. |
| G10 | Sub-items: Integrator, Min-Max (SUB_ITEM_DF) (task) |
passed | passed | Integrator adds value × seconds; TIME_UNIT ignored. |
| G10 | Block / unblock an item (ITEM_DF.BLOCKED via dssqld -m); write with itmval -o (task) |
passed | passed | blk flag, writes without -o silently ignored; ublk (updated blocked) after unblock (ISS-001, closed). |
| G10 | Trigger group, class (compile on load), object via quick load (task) | passed | passed | DEMO.COUNTER counts every second; full remove/load cycle clean. Phase 6: three classes and objects in one remove/load cycle, 0 errors. A class that fails to compile is not inserted (DSI-E-OPCCOMERR); error lines appear in LISTING after insert with COMPILE 0 and a compile update (test class removed). |
| P10/L10 | Traditional class with prompt/attribute, signal from SECTION, item created from a template, ERROR check, >=:, PRINT; attribute change via OBJECT_ATTR_VAL (task) |
passed | passed | CIENG_TANK / TANK1.CALC: volume 50→100, 82→164; capacity 0 refused; capacity 200→400 took effect on next run; created item and section deleted with the object. % in PRINT cuts the message (ISS-025). |
| P11 | Java class (task) | passed | passed | CIENG_JFLOW / TANK1.JFLOW: inflow 120→2, 90→1.5, systemMessage in umhlog.log from OPCJEXE. Created item keeps the identifier's case (…JFLOW.sPerMin). Worked without a class reset (ISS-029). |
| L10 | Change a class with objects: compile + reset (task) | passed | passed | Old code runs until reset (RESET_REQUIRED 1). opcdbg Reset class works (extra prompt for a report file); dssqld CLASS_DF.RESET does nothing, OBJECT_DF.RESET refused (ISS-028). |
| L10 | opcdbg read-only checks (task) |
passed | passed | Database check (one never-compiled foreign class SINUS), get class/object, object status/signals/attributes, executor main info. Dumps are not dssqld-readable (ISS-027). |
| G10/C10 | Authorization group and user creation (task) | passed | passed | Group CIENG_VIEWER (sample file 08_auth_group_df.qli) loaded/removed by Claude; test user CIENG_TEST (no password) loaded by the user, checked and removed. The sample creates no users. |
| C10 | String items: length 1–200, holds length − 1 characters (task) | passed | passed | Tested with temporary CI-Eng-Sample.DEMO.STR* items (removed): 201 rejected; too-long writes cut, status 12 OVERRANGED (ISS-019). |
| C10 | Integrator time unit: integration granule itm_int_secs in itm.sup (task) |
passed | passed | 60 → RUN_SECONDS +1 per minute; restored to 1 (file identical to backup), +1 per second again (ISS-010). Elevated restarts run by the user. |
| G10 | Displays, symbols, Operator Interface test | display done (phase 10); symbols not practiced | display added | Display CIENG_Tank built in the Edit Module and checked in the HTML display. |
| L41/C10 | Modbus TCP line, station, scan type, points, connected items by quick load (task) | passed | passed | Loopback to CI Server's own Modbus slave (eqpmdcmem + eqpmdcslvtcp on 5020, started by hand). Line load created and started EQPCIENG; removal stopped it and deleted its files. Write/read-back, off-scan/on-scan checked; full remove/reload from sample files. Protocol must be Open Modbus/TCP (ISS-024). Mirror start files copied to tls\com by the user; after a restart everything came back under the CI Service and the setpoint was re-sent on connect. |
| G10 | Alarms, reports, audit, RDBMS, history | alarms (phase 8), history (phase 9), reports (phase 11), audit (phase 12) done; RDBMS passed on a user R1.05 system (see the RDBMS row below) | alarms, history, reports, audit added; RDBMS n/a (tested in R1.05 only) | Covered in their own phases (7–12); RDBMS added 2026-10-02. |
| R10/R20 | Read a setup file: active settings and keyword help (task) | passed | n/a | Read-only. Compared with the Setup File Editor GUI for wfla_display.sup, wflgdi.sup and all 9 tabs of jwuiisg.sup: fields and values identical. Manual differences logged as ISS-012 to ISS-017 (installed software taken as the reference). |
| R10 | Check web access for CI View: ports, Remote Connect page, DEPLOY folder (task) |
passed | n/a | 8080/8443 listening, page 200, six DEPLOY folders. |
| R10/R20 | Change a setup file safely (task) | passed | n/a | jwuiisg.sup HTTP port 8080 → 8081 (text edit, elevated restart): 8081 served the page, 8080 refused; restored, hash identical to backup. Editor: OK writes at once, Reset Field restores the default (ISS-016). |
| R10 | Separate CI Portal node (licence, DURM line, dur.sup host node, copy displays) |
not practiced | n/a | Needs a second node. |
| R10 | Login method / login control | not practiced | n/a | Moved to dssana.sup (ISS-017); phase 5 (C10) and 13 (J40). |
| L45/E20 | OPC UA client → own OPC UA server loopback by quick load; certificate exchange; node IDs (task) | passed | passed | Station CIENG_UA (opc.tcp://localhost:34493, Basic256Sha256/SignAndEncrypt): UA.LEVEL_COPY follows TANK1.LEVEL (55, 62.5, 71, 33, 44.4), UA.SRV_STATE 0. Certificates trusted by the user (client side, then server side). Entity namespace urn:Yokogawa:CI_SERVER_OPC_UA_SERVER found by browsing OPCUAC_TAG_DF (ISS-032). Full remove/reload clean, reconnects without a new exchange. User configured a point in the Engineering Module: browse stores the item object, value node must be typed (ISS-033); test item/point removed afterwards. |
| L45 | ACCESS read-only checks: processes, ports, OPC UA server config/PKI, ODBC server (task) | passed | n/a | ISS-008 cause found: odbsrv cannot load its SSL certificate (folder tls\pki\odbsrv missing) and exits. |
| G10/C10 | RDBMS data exposure to SQL Server: SQL login, dbc.sup DEM_CONNECTION, DATA_EXPOSURE_DF, ITEM_DF.AGG_INTERVAL, SQL-side retention job (task) |
passed (R1.05 only) | n/a — tested in R1.05 only (user decision) | 2026-10-02 on the user's R1.05.00 system (not the R1.03 dev machine): 49 AID.WRPS.* items at 1 minute into a remote SQL Server 2022; rows survive a CI Server restart; 60-day purge job. Quoted filter field stopped DBCSND (ISS-057); ITEM_HISTORY not tested (ISS-058); SQL login needed (ISS-059); steady-item rows (ISS-060); folder rights (ISS-061). R1.03 dbc.sup and dataset definitions checked read-only (identical). |
| L30 | BUS utilities: durwfp, setup files (dur.sup, durm_1_udp.sup, time_table.sup, fmfprt.sup) (task) |
passed (read-only) | n/a | umhman, umhtestprog, umhmsg fail (ISS-030). Unlicensed run-time limit hit and documented (ISS-031). |
| L30 | MDUR node links, encryption, logical addresses, printer devices | not practiced | n/a | Single node, no printer devices. |
| L55 | CI Exchange for CENTUM VP / Prodigy | not practiced | n/a | Needs CENTUM VP (RGS, Vnet/IP) or Prodigy data. |
| L15/C20 | Acknowledgement type, area of interest, alarm selection area by quick load; ASA compile check (task) | passed | passed | CIENG_ACK (MANUAL matrix), CIENG_TANKS, CIENG_TANK1 compiled valid. Description > 78 characters refused; an ASA without spaces is stored with VALID_EXPRESSION 0; an ack type in use cannot be deleted. |
| L15/C20 | Item alarming, test alarm, ALARM_CURRENT / ALARM_CHRONO, acknowledge via dssqld -m on ALARM_CURRENT, delay and repeat (task) |
passed | passed | TANK1.LEVEL 85 → HIGH (Alarm 2, prio 2), 95 → HIGH HIGH; acknowledged by NAME/ACK; acknowledged return to normal cleared, unacknowledged one stayed; DELAY 5 s / REPEAT 10 s events as documented. Changing alarm fields auto-acknowledges a pending return to normal. No ALDPRT lines in umhlog.log (ISS-035). Full remove/reload clean. |
| L15 | ALARM Service read-only checks: processes, setup files, almdbg 1/9/10/12/14, alhdbg 1, ALH storage group; INFO event with almdbg 16 (task) |
passed | n/a | Destinations ALH, OPXUAS, ALNMGR, ALDPRT. alh.sup extra keywords, ALH lifetime 52 weeks (ISS-036). INFO event stored; some text columns hold leftovers (ISS-037). Two extra INFO events named name were created by a probe with default answers. |
| L15/C20 | First-out groups, alarm collections, shelving, link display, notifications, acoustic/count destinations | not practiced | n/a | Need displays (phase 10), a second alarm item design, an SMTP server or a logged-in sound session. |
| C20 | External alarms (EAL) from OPC UA A&C servers and CENTUM VP | not practiced | n/a | No A&C source or Vnet/IP on the test system. |
| E30 | Alarm System Performance Analysis (ASPA) | not practiced | n/a | GUI; the test system has too little alarm history for meaningful KPIs. |
| C40 | Item storage groups by quick load: Event/Item, Scan/Time, Aggregation; read per group (task) | passed | passed | CIENG_SCAN10S stored LEVEL/INFLOW every 10 s after the restart; CIENG_EVENT stored live writes; restart needed for new groups (ISS-006, closed). CIENG_AGG stayed empty until the scan group got priority 10, then 30-min max 77 / min 33 / avg 52.7 (ISS-040, closed). Full remove/reload with three groups: 0 errors (before the priority field was added; PRIORITY itself verified with dssqld -m). |
| L20 | hisdbg read-only checks and forced rollover (task) |
passed | passed | 45 groups, 30 clients; group/unit info; rollover of CIENG_EVENT closed unit 3,1. Extra history types 4 and 36 (ISS-039). |
| L20/L35 | ithloahis into older units (task) |
passed | passed | Samples in the active unit or a unit closed after the restart stored; older ones dropped silently (ISS-006); dropped sample became the next unit's initial value (ISS-038). |
| L20/C40 | Archive and retrieve, hasdbg, hisrecover, hiswrn, hisrep by hand |
not practiced | n/a | No archive device configured (has.sup); would change history administration. |
| C50 | Build a display in the Edit Module, check the XML (task) | passed | passed | User built CIENG_Tank (HTML mode): text, number field, alarm overview, trend. File stores item name + id; after a sample reload (id 248 → 268) validation still passed and a new session showed live values. |
| C50/R30 | Deploy/remove, jwuiutl HTML export, validate, search; HTML display in the browser (task) |
passed | passed | Scripts displays/deploy_displays.cmd / remove_displays.cmd; command-line HTML identical to the Edit Module's. Number field live in the browser; HTML trend draws no line (ISS-041). Browser page reload ends the session; the display menu View > Reload keeps it (user). |
| R30/C50 | Operator layout CIENG_Operator (menu, toolbar, navigation/main/banner frames, status line) added with layout.ps1; navigation display CIENG_Menu; open displays in frames, layouts and the popup layout (task) |
passed | passed | Desktop: second 1600 x 900 window, frame navigation and Back, popup on top and minimised with its parent, F11 within taskbar limits; the Operator Interface must be restarted after Layouts.xml changes; factory default layout unchanged for Admin. Web: ?d=CIENG_Tank&l=CIENG_Operator. Status line/command names not in the readme (ISS-042). A stray trend property connection caused a desktop error (ISS-041 update). |
| R30/C50 | Layout parameters one by one on test layouts (LT_*): frames, window options, menu/toolbar/status line, all commands (task §6) |
passed | n/a | 2026-10-02. Desktop via jwuipoi -layout, web via &l=; popups, modal, maximumOpen via launcher display LT_Launcher. Tabs on LT_Tabs*. Readme differences and web limits: ISS-062..067. Not tested: print orientation/margins, playback, multi-screen positions, the maximumTabs limit for new tabs. Test layouts need no project data (not added to CI-Eng-Sample). |
| C50/R30 | Trend settings one by one on CIENG_TrendLab (pen source, type, scale, axis, grid, limits; time range, performance, appearance, time axis, legend, pen panel; property sheet listed) (task) |
passed (desktop) | passed | 2026-10-02, user confirmed each round with screenshots. Pen limits, pen title and backgroundPaint had no effect (ISS-056). Internal items need trend_feed.ps1 after a restart. |
| C50/R30 | HTML trend: cause of the empty web trend and 50-pen workaround (add_trend_spares.ps1); Micro Trend (task §6) |
passed (workaround) | passed | Web code always builds 50 columns (ISS-041). Padded CIENG_TrendLab draws in the browser with a clean legend; web ignores Show in legend (ISS-056). Micro Trend drew once, then blank (ISS-055). |
| C50/R30 | Web check of each trend setting (4 batches on a padded scratch copy, checked in the browser by Claude) (task §6) | passed | passed | 2026-10-02. Works / ignored / different table in the task; matches IM 36K10C50 Table 2.27-28 except timeShift (error message) and Show in legend (ISS-056). A hidden real pen breaks the 50-pen workaround (confirmed). |
| C50 | Remaining trend settings: custom time range, Rendering3dOrt, RenderingCSS (task §4) |
passed | passed | 2026-10-02. Custom range on desktop and web (desktop: no live update); 3dOrt draws black lines; CSS mode makes the display unloadable. |
| R30/C50 | Sample operator HMI: 8 generated CIENG_* displays, layouts CIENG_Operator (header, tab set, banner) and CIENG_Popup, live-data feed with server-side Start / Stop (sample README, layouts §6.6) |
passed | passed | 2026-10-06 on desktop and web. Replaces CIENG_Tank, CIENG_Menu, CIENG_TrendLab. Tab sets: last child of the frame set (ISS-069), desktop zoom via navigate … stretchDisplay (ISS-070), one layout command at a time (ISS-071), connectionState breaks the web layout (ISS-068). |
| C50 | Writing display XML directly: text size, rounding, arc angles, web item attributes, server-side command, alarm overview columns (task) | passed | passed | 2026-10-06, test display CIENG_Test (removed) on both clients; arc angles clockwise from 3 o'clock on both clients (an earlier note on mirrored angles was wrong); jwuiutl -v re-saves (ISS-075). |
| C10 | Sample user CIENG with empty password via quick load, profile layout and initial display (task) |
passed | passed | 2026-10-06: PASSWORD "" needed (ISS-072); web logon uses the profile layout (ISS-074); group removal with an open session stopped DSSSDA03 (ISS-073). Factory group OPERATOR is enough for the server-side Start. |
| J10/C50 | Restart CI Server with the Edit Module open | observed | n/a | Start aborted: JWUIGED<pid> still attached to the BUS Service (ci_start.log); closing the Edit Module fixed it (skill system-check). |
| R30/C50/C60 | Dataset forms, symbols, AOG library, dual screen, per-user layouts | not practiced | n/a | GUI work; user profiles not changed. |
| R40/C30 | REPORT Service checks: processes, set-up files (rptman.sup, rptge1.rpt, rptgen.rpt), system reports, rptstp (task) |
passed | n/a | Read-only plus one cancel: rptstp rptge1 stopped the endless-loop test report CIENG_LOOP (removed). 28 system reports; two names differ from the manual (ISS-043). |
| R40/P20 | RQL in the interactive generator (rptgen -s rptgen.rpt), CSV with SPOOL (task) |
passed | passed | Piped query files (bash <, PowerShell via cmd /c); @NEXT 0 needed; dates are local-time seconds; LOOP refused interactively (RPT-E-LPNOTAL); aggregated history empty on the test system. |
| C30/P20 | Report definitions by quick load: ad hoc with parameters, daily schedule, item trigger, HTML with cursor loop, logbook; generate, read, print, delete; remove (task) | passed | passed | CIENG_TANK1, CIENG_INFLOW_HI, CIENG_HTML + destination CIENG_FILE; full sample remove/reload 0 errors. Schedule ≥ 10 min, scheduled report not deletable until the schedule is cleared, CORRECT_DAYLIGHT (ISS-044); dssqld ad hoc without ADHOC_DEST logs a print error (ISS-045). User checked the Engineering Module: forms, generate dialog (item browser not filtered, ISS-048), view of text and HTML reports. |
| C30 | File printer device and destination (task) | passed | passed | Output type needs the node name (<node>:FILE); literal path only (%TLS_LST_PATH% failed). Sample builds the file at load (17_printer_df.ps1). |
| L50/P30 | DSS tools: processes, dss.sup, quick load macro/include/memo file, dssutl read, DSS compiler syntax check (task) |
passed | n/a | Memo from file: absolute path ≤ 82 characters only (ISS-046). Dictionary untouched. |
| C30 | Report component on a display, hardcopy printer, extra report generators | not practiced | n/a | GUI / no printer / admin restart. |
| E10 | Excel Add-in (DART) | not practiced | n/a | Excel not installed on the test system. |
| J20 | HAC checks: licence, processes, hac.sup, scripts, HMI properties, logs (task) |
passed (read-only) | n/a | No hacini.sup, normal ci_start, CI_PRIM unset: HAC not used; template hac.sup differs from the manual (ISS-053). |
| J20 | Redundant pair set-up, switchover, patching; stand-alone Recovery and journaling (task, task) | not practiced | n/a | Needs two licensed servers; stand-alone Recovery not started (default actions restart tools). |
| J40/C10 | Login methods and the No-login profile (task) | passed (read) | n/a | No login without a matching user = full authorization (ISS-018). |
| J40 | Active Directory integration and SPNEGO single sign-on (task) | not practiced | n/a | No domain on the test system; extra AD keywords installed (ISS-054). |
| L25 | AUDIT Service checks: processes, ADT group, classifiers, selection groups (task) |
passed | n/a | adtsto + adtcol; 463 classifiers, 444 stored; ADT lifetime 52 weeks; manual differences ISS-051. |
| L25 | Read the audit trail: export, RQL, audit report, what each tool records (task) | passed | passed | Report CIENG_AUDIT (19_audit_df.qli); qli export needs NAME in @FIELDS; dssqld = ENT-ENG-MOD, Engineering Module = LOC-ENG-MOD (checked by the user); itmval not audited (ISS-049). |
| L25 | Classifier STORAGE, selection groups, event logger ADTLOG (task) |
passed | passed | Selection group CIENG_ITEMS compiles on load; adtlog -n adtlogci with sample setup file printed only CI-Eng-Sample events; storage flag cached (ISS-050); AUDIT_INFO effect not shown (ISS-049). Full sample remove/reload 0 errors. |