Full manual diffs (C50, R30, C60, L20, C40, L35, R10, R20, J10, L30, L50, P30, G10, C10) and read-only checks on the shared R1.05 test server where the permission system allowed them. Skills and summaries moved to R1.05. Issues ISS-092..129 (gaps 104-107, 114-115, 130-131 unused); ISS-074 closed (manual and software agree), ISS-091 corrected by ISS-119. version-differences: unlisted manual changes and installed-only changes. r105-verification: V5-V9 and new not-tested rows. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
3.9 KiB
| task | version | source | status |
|---|---|---|---|
| Load item history from CSV (ithloahis) and read history back (dssqld) | R1.05 (first written for R1.03) | IM 36K10J10-01EN §2.9.2; IM 36K10L50-01EN §3.6 (5th ed., Feb. 2026); practiced with CI-Eng-Sample 2026-09-30 (R1.03) | verified on R1.03 (2026-09-30); on R1.05 `ithloahis` is installed but loading was not re-run (it writes history and the reduced CI-Eng-Sample load on the shared R1.05 test server has no storage group) - awaiting user verification |
Load item history (ithloahis) and read it back
Writes to the history database. Needs CI Server running and the items linked to an
item storage group of type Event/Item or Event/Event. The sample project provides
CIENG_EVENT with CI-Eng-Sample.TANK1.LEVEL and .INFLOW.
Before loading
- A new storage group stores nothing until CI Server has been restarted (stop, then start the CI Service). Restart after creating a group.
- Samples are stored into the active unit or an earlier unit opened by the storage process
since the last restart (e.g. one closed by a forced rollover). Samples older than the first
unit opened after the restart are dropped without any message, even with
-l, and even when an older unit's time range covers them (verified 2026-10-01, ISS-006). A restart closes the active unit and starts a new one, so load old data before restarting, or not at all. Check the unit times first: skillhistory-management, taskhistory-checks.md. - A dropped sample dated shortly before the first unit after the restart (same day) becomes the initial value of the next unit at the next rollover, instead of the item's live value (reproduced twice; a sample one day older did not do this, ISS-038). Check the result after loading, and do not load samples older than the active units.
- Loaded samples appear in
ITEM_HISTORYa few seconds afterithloahisreturns.
Input files
Event file: one sample per line.
EVENT
<time>,<item>,<value>
1790739700,CI-Eng-Sample.TANK1.LEVEL,47
Scan file: several items per line (max 100), one line per timestamp.
SCAN,CI-Eng-Sample.TANK1.LEVEL,CI-Eng-Sample.TANK1.INFLOW
1790739715,61,101
1790739720,62,102
Time is seconds since 1970 (UTC), optionally with a fraction, or a date text such as
29-Apr-14 11:48:17.452. Quotes and spaces around fields are optional. A blank value in a
scan line is skipped.
Load
ithloahis -f <file>.csv -v
-vshows progress (Handle event based table,item … on column n).-t GMT|LST|LCTsets how text times are read (default GMT).-s <section>puts a section in front of every item name.-ialso updates the item's current value (can raise alarms and trigger objects; loads the system). Without it, only history is written.
Read history back
ITEM_HISTORY is not exported by default; use a filter file that names the item and a
time range, otherwise nothing is returned:
@SELECT
'ITEM_NAME = "CI-Eng-Sample.TANK1.LEVEL" and SAMPLE_TIME > "30-09-2026 00:00:00" and SAMPLE_TIME < "01-10-2026 00:00:00"'
@ITEM_HISTORY
dssqld -e history.qli <filter>.qli -c -l history.qlo
Result columns include NAME (<group>:<item>/<time>/Value), SAMPLE_TIME, ITEM_VALUE,
QUALITY. Values written live (e.g. with itmval -p) and the value at CI Server start also
appear.
R1.05 check (awaiting user verification)
On a system where the CI-Eng-Sample storage group CIENG_EVENT exists (full sample load,
then a CI Server restart): load the SCAN example above with ithloahis -f <file>.csv -v, then
read it back with the ITEM_HISTORY filter. Expected as on R1.03: the three LEVEL / INFLOW
samples appear in ITEM_HISTORY a few seconds after the load. The manual text for ithloahis (J10 §2.9.2) is unchanged.
Verified (CI-Eng-Sample, R1.03, 2026-09-30)
SCAN load of LEVEL 61–63 / INFLOW 101–103 and EVENT load of LEVEL 47, 48 were all read back with the filter above.