Read-only re-check on the shared R1.05 test server plus a diff of the R1.03 and R1.05 manual editions. - installation-security: R1.05 OS list, Defender exceptions, IT security 2.0/3.0, LAPS, automatic configuration merge (jupgutl), PRM chapter, port 34597; setup_check.ps1 gets -Version (default 1.05.00). - data-access: L45 renumbered (new ch. 4 RESTful API), extended OPC UA functions off by default, OPC UA methods (OPCUAC_METHOD_CALL2_DF), Information Model Mapper, ServerConfig.xml in %TLS_SAV_PATH%. - equipment: Modbus unchanged; IEC 104/61850 run as EQT managers (eqtdbg, eqtfrcscn), IEC 61850 report control blocks, upgrade steps. - Issues ISS-076..090; R1.05 notes on ISS-003/008/032/034/061; progress and version-differences updated. Co-Authored-By: Claude Opus 5.5 <noreply@anthropic.com>
8.5 KiB
manual: IM 36K10E20-01EN title: OPC Interface edition: 4th Edition, Feb. 2026 (R1.05); first summarised from the 2nd Edition, Sep. 2023 (R1.03) version: R1.05 (first written for R1.03) status: from docs. R1.03 (2026-10-01): OPC UA point and certificate forms compared with quick load on the test system (user configured a point in the Engineering Module, exported and diffed). R1.05 (2026-10-08, read-only): method and mapper datasets, installed mapper files, AOG method displays and the ServerConfig.xml location checked; forms not opened, nothing configured
OPC Interface (R1.05)
Engineering Module procedures for OPC Classic, OPC UA client, the OPC UA Information Model
Mapper (new in R1.05) and OPC UA PubSub. Concepts, setup files and the OPC servers:
IM36K10L45-01EN.md. Client and PubSub objects are under Configuration → I/O processing →
Equipment → (OPC DA client | OPC A&E client | OPC UA Client | OPC UA PubSub). CI Server must be
running. Section numbers refer to the 4th edition (R1.03 §2.2.6 is now §2.3, PubSub moved from
ch. 3 to ch. 4).
1. OPC Classic (§1)
- DA: line (equipment node, process name — the manual says it must start with
OPCfor DA and A&E lines,OPXfor OPC UA), station (OPC server node and ProgID, status item), group (deadband, requested update rate, status item), point (external relation, group, OPC tag, browse). Then connect items to points (Tutorial "Define points"). - A&E: line, station (server, subscription filters; category filter = event category codes of the A&E server, comma separated), subscribed attributes; to show events in the current alarm overview, map event sources to items. External names must be unique per station.
2. OPC UA client (§2.1)
Order: line → station → subscription → points (→ methods) → alarm components / event type
filters / event nodes / template settings (only when alarms are wanted; no alarms are received
until event nodes are configured, and since R1.04 only with OPXC_ENABLE_EXTENDED_FUNC = YES,
see IM36K10L45-01EN.md §6).
| Object | Key fields (dataset field) |
|---|---|
| Line | name ≤ 31, equipment node (None = this node), process name starts with OPX, ≤ 11 characters (EQUIPMENT_MAN) |
| Station | name ≤ 19; Host(:port) + Discovery fill session/server name and endpoint, or type the endpoint (SERVER_01_ENDPOINT); redundant servers + Active server item (0 none, 1 server 1, 2 server 2); On scan; General communication status item (STATUS_ITEM; 4th ed. lists 0 preparing, 1 connected, 2 comm error/reconnecting, 3 connect failed, 4 shutdown received, 5 connection recreated — a Boolean item worked on R1.03, ISS-080); security policy and mode; anonymous or user/password; requested session time-out; alarm tab (request active alarms, store all alarms as SOE, severity → priority mapping) |
| Subscription | publishing interval, lifetime and keep-alive counts, max notifications, priority, publish enabled, status item |
| Point | external relation Input / Output / Input + Output; subscription; Namespace, Node id type, Node Id (or Browse path; F5 rebrowses); Read additional node information (R1.05; clear it for slow links); read-only Last value, Data type, Access level, Value rank; array element; options (own sampling interval, monitoring mode, queue size); conversion (offset, step) |
| Method (§2.1.6) | name (≤ 255), namespace, node ID type, node ID (or browse path); Options: parent object node ID set by hand; Arguments: input/output argument types set by hand (use the server's types). Dataset OPCUAC_METHOD_CALL2_DF. No process areas any more (set them on the method object's MTD_TRG signal) |
Alarm event types (§2.1.4): GeneralModelChangeEventType and, only with
OPXC_BASE_MODEL_CHANGE_EVENT set, BaseModelChangeEventType.
Upgrade from R1.03 (§2.1.6): methods with String or Boolean input arguments must be refreshed —
edit any field and Apply (rebrowse), or copy the method, set the arguments, delete the old one
and add the copy. Running a method needs a CI Server object (IM 36K10L45 5th ed. §10.6; skill
data-access, opcua-client.md §7).
Observed on R1.03 (2026-10-01): in the point form's browse, picking the item itself
(Objects/<section>/…/<item>) stores the item object ({"nsid":"<n>"}), which has no
value: Last value/Data type stay empty and the point is never monitored (revised sampling
interval 0, item status 13). Expanding the item and picking its Value node works
({"0":"Value","nsid":"<n>"}, verified by the user). For quick load type the stable form:
{"0":"Value","itnm":"<item>"} (namespace urn:Yokogawa:CI_SERVER_OPC_UA_SERVER, type
STRING). The form also fills OPC_DISPLAY_NAME and OPC_TAG_INFO (browse bookkeeping;
not needed for quick load). ISS-033.
3. Certificates (§2.2, §2.3)
OPC UA Client → Certificates: Trusted, Rejected (server certificates arrive here), Own certificate. Trust = open the rejected certificate, tick Trusted, Apply; reject = untick. Restart the Engineering Module to refresh the folders. Modify the own certificate (name, organisation, country, domain or IP, RSA key strength, signature algorithm, validity).
New in R1.05 (§2.2): the client warns in the Historical Alarm Overview and the UMH message log
when its own or the server's certificate is about to expire (lead time = hidden
OPXC_CERT_EXP_PERIOD_WARN, 2 months in the installed epauac_eqp.sup, verified 2026-10-08).
CI Server OPC UA client ↔ CI Server OPC UA server (§2.3): trust the server certificate
on the client; copy the client's own certificate
(%TLS_ALLUSERS_PATH%\pki\opxuac\pkiclient\own\certs) to the server's
…\pki\opxuas\pkiserver\trusted\certs; the manual also asks to tick Use CI Server entity names
for nodeids in opxuas.sup and restart the server. On the R1.03 test system the loopback
worked without that option, using itnm node IDs (ISS-032).
4. OPC UA Information Model Mapper (ch. 3, App. 1; new in R1.05)
From docs; installed parts verified on R1.05 (2026-10-08): dataset UASERVER_MAPPER_DF,
%TLS_WAP_PATH%\cfg\tools\uamapper\ with libraries UAMapperLibrary_MDIS, _None,
_Use_model.
- Purpose: publish CI Server data under a standard OPC UA information model (NodeSet file, e.g.
MDIS or PA-DIM) instead of, or next to, the native CI Server model (server side:
IM36K10L45-01EN.md§7). - Rights:
UA_MAPPER_PROJECT_INSERT,_MODIFY,_DELETE(already inSYSTEM_MANAGER). - Workflow (Tools › OPC UA Information Model Mapper): New Mapping (folder
%TLS_WAP_PATH%\cfg\tools\uamapper\mapperprojects\<name>) → Configure: NodeSet file (base models in the same folder) and optional library template → Edit Rules: per OPC UA object type a selection query on CI Server objects or sections (CLASSNAME = …,SECTIONNAME = …; SQL keywords in App. 1), then methods → class names, variables → tag names, events → item or external alarm names → Build (results can be exported to / imported from CSV;MappingReport.txt) → Load to an OPC UA server process. Removing a mapping does not unload it from the server (§3.4.6). - Rule-based mapping needs consistent naming or class/object engineering; otherwise map by CSV.
In enterprise engineering, map on each CI Core. The manual advises trying a mapping on an
extra OPC UA server instance first (§3.4; instance procedure in
IM36K10L45-01EN.md§7,<instance>_ServerConfig.xmlin%TLS_SAV_PATH%). - Dataset
UASERVER_MAPPER_DF:NAME,DESCRIPTION,UA_NAMESPACE,UA_MODEL_FILE,LIBRARY_NAME,MAPPING_FILE,TARGET_UA_SERVER,PROJECT_STATE(INIT, CONFIGURED, MAPPED, DEPLOYED).
5. OPC UA PubSub (ch. 4)
UDP publish/subscribe of Data Access values from the CI Server OPC UA server address space
(OPC visible items). Needs OPXUAS_ENABLE_EXTENDED_FUNC = YES since R1.04
(IM36K10L45-01EN.md §7). Objects: line, published datasets, station, writer groups + dataset
writers (publisher), reader groups + dataset readers (subscriber), then Upload dataset
configurations to runtime. Each extra PubSub line needs its own OPC UA server instance named
like the line's server name (own <instance>_ServerConfig.xml, which R1.05 keeps in
%TLS_SAV_PATH% — R1.03: tls\exe; ISS-081). Limits per line: 4 stations, 8 writer groups,
8 reader groups, 32 dataset writers, 32 dataset readers, 32 published datasets. Status mapping
as for the server (NORMAL → Good; NOT_INIT, UPD_OFF, OFFSCAN, OFFLINE → Uncertain; BAD_VALUE →
Bad). Not practiced (needs a PubSub peer).